7.5 Three-Phase Split System Air Conditioner 11.2 EER/14.8 IEER/R-410A
Standard Features
• Two-stage energy efficient compressor
• Quiet operating top discharge
• High-efficiency copper tube / aluminum fin coil
• Brass liquid and suction service valves
• High- and low-pressure switches
• Factory-installed filter drier
• Complies with ASHRAE 90.1
• AHRI Certified; ETL Listed
DX14XA 0903A* | DX14XA 0904A* | DX14XA 1203A* | DX14XA 1204A* | |
Cooling Capacities | ||||
Nominal Cooling (BTU/h)¹ | 90,000 | 90,000 | 115000 | 115000 |
EER / IEER | 11.2 / 14.8 | 11.2 / 14.8 | 11.2 / 14.8 | 11.2 / 14.8 |
Decibels | 83.7' | 83.7' | 84.7' | 84.7' |
AHRI | 210605692 | 210605693 | 210605694 | 210605695 |
Compressor | ||||
RLA | 26.9 | 12.0 | 32.6 | 14.8 |
LRA | 164 | 94 | 240 | 130 |
Condenser Fan Motor | ||||
Horsepower | 1 | 1 | 1 | 1 |
FLA | 7.00 | 3.50 | 7.00 | 3.50 |
Refrigeration System | ||||
Liquid Valve Connection Size (“O.D.) | ⅝" | ⅝" | ⅝" | ⅝" |
Suction Valve Connection Size (“O.D.) | 1⅜" | 1⅜" | 1⅜" | 1⅜" |
Valve Type | Sweat | Sweat | Sweat | Sweat |
Refrigerant Charge (oz.)² | 55 | 55 | 55 | 55 |
Electrical Data | ||||
AC Volts | 208/230 | 460 | 208/230 | 460 |
Hz / Phase | 60 Hz/3 | 60 Hz/3 | 60 Hz/3 | 60 Hz/3 |
Minimum Circuit Ampacity ³ | 40.6 | 18.5 | 47.7 | 22.0 |
Max. Overcurrent Protection 4 | 60 | 30 | 80 | 35 |
Min / Max Volts | 197/253 | 414/506 | 197/253 | 414/506 |
Electrical Conduit Size | ½" or ¾" | ½" or ¾" | ½" or ¾" | ½" or ¾" |
Ship Weight (lbs) | 325 | 325 | 345 | 340 |
¹ Tested and rated in accordance with ARI Standard 208/230 2 Factory Holding Charge. Follow Instllation Instructions for system charge 3 Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes 4 Must use time-delay fuses or HACR-type circuit breakers of the same size as noted. Notes • Always check the rating plate for electrical data on the unit being installed. • Installer will need to supply ⅞" to 1⅛" adapters for suction line connections. • Unit is charged with refrigerant for 15’ of ⅜" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure. |